Customization: | Available |
---|---|
Type: | Central Air Conditioners |
Capacity: | 70K BTU |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GREE Modular GMV5 Heat Recovery series with modular installation capability design of up to 180kW in combination to the wide range of indoor unit choices offers an advanced solution for medium and big commercial applications. GMV-Pdhm heat recovery series breaks the limits of classic VRF applications, since indoor units can operate under both cooling and heating operation at the same time. Energy saving takes place from the recovery of energy that would be traditionally released in the environment, that is uniquely recovered and channeled for the alternative operation purpose in spaces that require it and vice versa, under five different operation combinations.
Wide temperature operation range. The units can operate in a wide ambient temperature range decreasing thus capacity loss due to outdoor temperature.
GMV 5 offers an increased level of installation versatility due to the big height and length of piping, as well as wide range of indoor units to choose from.
The combined COP (ECOP) can reach 6,8 during recovery mode, the highest available in VRF applications.
TECHNICAL SPECIFICATIONS | UNIT | GMV-Q224WM/E-X | GMV-Q280WM/E-X | GMV-Q335WM/E-X | GMV-Q400WM/E-X | GMV-Q450WM/E-X | ||
RATED COOLING CAPACITY | kW | 22.40 | 28.00 | 33.50 | 45.00 | |||
Btu/h | 76432 | 95540 | 114307 | 136486 | 153546 | |||
RATED HEATING CAPACITY | kW | 25.00 | 31.50 | 37.50 | 45.00 | 50.00 | ||
Btu/h | 85304 | 107482 | 127955 | 153546 | 170607 | |||
EER | kW/kW | 4.09 | 3.44 | 4.04 | 3.36 | 3.04 | ||
COP | kW/kW | 4.75 | 4.32 | 4.87 | 4.5 | 3.94 | ||
POWER SUPPLY | V-Ph-Hz | 380-415/3/50-60 | 380-415/3/5060 | 380-415/3/50-60 | 380-415/3/50-60 | 380-415/3/50-60 | ||
CIRCUIT BREAKER | A | 20 | 25 | 32 | 40 | 40 | ||
POWER CONSUMPTION | COOLING | kW | 5.48 | 8.15 | 8.30 | 11.90 | 14.80 | |
HEATING | 5.26 | 7.30 | 7.70 | 10.00 | 12.70 | |||
MAX NO. OF SUPPORTED INDOOR UNITS | / | 13 | 16 | 19 | 23 | 26 | ||
REFRIGERANT | / | R410A | R410A | R410A | R410A | R410A | ||
REFRIGERANT CHARGE VOLUME | kg | 6.2 | 7.1 | 9.6 | 11.1 | 11.6 | ||
SOUND PRESSURE LEVEL | dB(A) | 60 | 61 | 63 | 63 | 63 | ||
CONNECTING PIPE | LIQUID | Inch | 3/8 | 3/8 | 1/2 | 1/2 | 1/2 | |
LOW PRESSURE GAS | 3/4 | 7/8 | 1/1 | 1/1 | 1 1/8 | |||
HIGH PRESSURE GAS | 5/8 | 3/4 | 3/4 | 7/8 | 7/8 | |||
DIMENSIONS (WxDxH) | OUTLINE | mm | 930/765/1605 | 930/765/1605 | 1340/765/1605 | 1340/765/1605 | 1340/765/1605 | |
PACKAGE | mm | 1010/840/1775 | 1010/840/1775 | 1420/840/1775 | 1420/840/1775 | 1420/840/1775 | ||
NET WEIGHT | kg | 233 | 233 | 302 | 346 | 346 | ||
GROSS WEIGHT | 243 | 243 | 317 | 361 | 361 |